Failure Modes

The failure mode is the way in which a failure is observed on the failed item. The failure mode describes how the failure occurs and what the malfunction is. For example, an electrical motor is not turning.

ISO 14224 prescribes the following best practice failure modes:

Failure mode type Failure mode Suggested failure mode code Description of the failure mode
Desired function not obtained External leakage 01-ELU

For example oil leakage

Failure to connect 01-FCO Failure to connect
Failure to rotate 01-FRO Failure to rotate
Failure to close on demand 01-FTC Doesn't close on demand
Failure to function on demand 01-FTF Failure to respond on signal or activation
Failure to function as intended 01-FTI General operation failure
Failure to open on demand 01-FTO Doesn't open on demand
Failure to start on demand 01-FTS Doesn't start on demand
No output 01-NOO No output
Plugged or choked 01-PLU Partial or full flow restriction
Structural deficiency 01-STD For example burst, rupture
Failure to stop on demand

01-STP

Doesn't stop on demand
Specified function lost or outside of acceptable limits Abnormal instrument reading 02-AIR False alarm, faulty instrument indication
Delayed operation 02-DOP Opening or closing time below specification
Erratic output 02-ERO Oscillating, hunting, instability
Failure to disconnect 02-FDC Doesn't disconnect on demand
Faulty output frequency 02-FOF Wrong or oscillating frequency
Faulty output voltage 02-FOV Wrong or unstable output voltage
High output 02-HIO Overspeed or output above acceptance
Insufficient heat transfer 02-IHT Cooling or heating below acceptance
Internal leakage 02-INL Oil leakage
Low oil supply pressure 02-LBP Low oil supply pressure
Load drop 02-LOA Load drop
Loss of buoyancy 02-LOB Loss of buoyancy in idle position
Low output 02-LOO Delivery or output below acceptance
Loss of redundancy 02-LOR One or more redundant units not functioning
Parameter deviation 02-PDE Monitored parameter exceeding limits, for example high or low alarm
Plugged or choked 02-PLU Obstructed piping
Power or signal transmission failure 02-PTF Power or signal transmission failure
Spurious high alarm level 02-SHH For example 60% of the lower explosion limit (LEL)
Spurious low alarm level 02-SLL For example 20% of the lower explosion limit (LEL)
Slippage 02-SLP Wire slippage
Spurious operation 02-SPO Unexpected operation
Structural deficiency 02-STD Material damages including cracks, wear, fracture, corrosion
Unexpected shutdown 02-UST Spurious stop
Very low output 02-VLO Delivery or output far below specifications
Failure indication is observed, but there is no immediate and critical impact on asset function Abnormal instrument reading 03-AIR For example wrong oil level indication
Breakdown 03-BRD Serious damage for example seizure or breakage
External leakage - fuel 03-ELF External leakage of supplied fuel
External leakage - process medium 03-ELP External leakage of oil, gas, condensate, water
External leakage - utility medium 03-ELU External leakage of water, lubricant, barrier oil
Internal leakage 03-INL Internal leakage of process or utility fluids
Noise 03-NOI Abnormal or excessive noise
Overheating 03-OHE Overheating of machine parts, exhaust or cooling water
Plugged or choked 03-PLU Flow restriction due to contamination, objects, wax
Minor in-service problems 03-SER Loose or missing items, discolouration, dirt
Structural deficiency 03-STD Material damages including cracks, wear, fracture, corrosion
Vibration 03-VIB Abnormal or excessive vibration

Also refer to Failure Mode Types.